Written question asked by Steve Reed (Labour) on Thursday, 17 January 2019, in the House of Commons. It was due for an answer on Tuesday, 22 January 2019 (named day). It was answered by Kit Malthouse (Conservative) on Tuesday, 22 January 2019 on behalf of the Ministry of Housing, Communities and Local Government.


Offices: Insulation

Question

To ask the Secretary of State for Housing, Communities and Local Government, whether desktop studies can still be used in lieu of tests as a route to compliance for combustible materials on high-rise offices.

Answer

Such assessments are no longer acceptable for buildings subject to the ban on combustible materials in external walls in regulation 7(3) of the Building Regulations. For buildings outside the scope of the ban such as hotels and offices, the current requirements for limited combustibility or for the whole wall system to have passed a BS 8414 test apply.

A new standard for assessments relating to the BS 8414 cladding test is currently being drafted.